Permit #B1902940
Address4041 CAMPBELL AVE
TypeCTBO
StatusFINALED
Permit HolderF & R CONSTRUCTION INC
OwnerSTREET RETAIL INC DIR OF PROP ANALYSIS
Applied Date10/11/2019
Approved Date11/21/2019
Date Issued11/25/2019
DescriptionINTERIOR RENOVATION TO EXISTING BUILDING TENANT: TACO AND PINA 1ST FLOOR GRADE LEVEL (UNIT 370

  View Event Log.      View Status.       View Required Plan Review       View Printer Version.   
  
  
Search Again

 
ReviewBuilding
Review Date10/24/2019
StatusRejected
Comments
COMMERCIAL PLAN REVIEW
All projects are reviewed under the requirements outlined in the Virginia Uniform Statewide Building Code. A written response letter must accompany plan revisions. Please contact the Plans Examiner for any clarification of the comments.
Permit #    B1902940
Applicable Code    VCC 2015 Edition
Project:    TACO + PIÑA RESTAURANT
Address:    4041 Campbell Avenue
Review Date:    24 October 2019
Plans Examiner:    Eric Rice-Johnston, Building, Accessibility
Email: erice-johnston@arlingtonva.us
Phone Number: 703-946-8953
1.    Revise the Accessibility Compliance Form. Box #2 may apply to the kitchen, but is inappropriate for areas open to the public. VEBC §404.3
2.    A001, Key Plan & Site Plan: Provide sufficient detail to demonstrate the egress route to the outside via the kitchen back door. VCC §1003.6
-    Show the location and distance to the Common Area toilet facilities noted on A002.
3.    A002, Code Analysis, Applicable Building Codes: Update the codes to the current edition of the Virginia Existing Building Code, Virginia Construction Code and the components thereto. ANSI A117.1-03 should be updated to -09.
4.    A002, Detail 1, Egress Plan: Two egress paths are required because the tenant occupant load exceeds 50 people. VCC Table 1006.2.1
-    The route through the kitchen is permissible for one of the exit paths. VCC §1016.2.5x3.
-    The route through the kitchen shall be at least 44" clear width. This is particularly important between hot cooking appliances and with the other hazards present.
5.    A102, Proposed Plan: Show where accessible seating is/can be provided. Note that at least one space is required for each different experience provided: table/booth service, bar seating, window seating. VCC §1108.2.9.1
6.    A102, Existing ADA Toilet Elevations:
-    Horizontal grab bars shall be set at 33" to 36" from the floor to the top of the gripping surface. ANSI A117.1 §609.4
-    The flush lever shall be located on the open side of the water closet. ANSI A117.1 §604.6
-    The bottom edge of the reflecting surface of the mirror shall be no higher than 40" above the floor. ANSI A117.1 §603.3
Additional concerns may come to light as these items are addressed.
-- end --
  



  
 